Reverse Osmosis Integrated System Single Pass/Double Pass
ROC-200 series reverse osmosis application control integrated system is in conformity with the needs of the integrated water treatment process control system transformation and upgrading. The system uses a 7-inch color touch screen as the main operating platform. Water quality measurement parameter collection, RO single/double process control process is highly integrated.
Description
ROC-200 series reverse osmosis application control integrated system is in conformity with the needs of the integrated water treatment process control system transformation and upgrading. The system uses a 7-inch color touch screen as the main operating platform. Water quality measurement parameter collection, RO single/double process control process is highly integrated.
The controller integrates various detection methods such as RO system operation programs, DI/DO control, water quality, and flow detection. RO controllers are available all at once.
ROC-210 is a single-stage reverse osmosis application control integrated system, and the ROC-220 is a two-stage reverse osmosis application control integrated system that satisfies users’ different process options. The flow meter and conductivity sensor configuration can be selected based on single and double stages
Feature
*Reverse osmosis measurement and control integrated machine, integrated measurement, process control, display function as one unit;
*7-inch Touch screen displays process flow and parameter settings;
*All-in-one integrated reverse osmosis automatic control function, no need to be equipped with PLC and other equipment;
*Human-machine interface combines measurement display, process parameter setting, consumable management, data query and other functions;
*Pane I mount, su i tab I e for sma I I and medium reverse osmosis systems;
*Can provide personalized and customized products according to customer processes and needs
Application
Applicable to a variety of small and medium-sized single-stage, two-stage reverse osmosis application control integrated system. Simple operation, complete measurement configuration, and highly integrated system.
Technical Parameter
ROC-210 Single Pass RO Control Systems | ROC-220 Double Pass RO Control Systems |
Measurement parameters: | |
Conductivity: Feed Water, Primary Produce Water | Feed Water, Primary Produce Water , Secondary Produce Conductivity |
Flow Rate: Feed Flow, Primary Produce Flow, Primary Concentrated Flow | Feed Flow, Primary Produce Flow, PrimaryConcentrated Flow ,Secondary Produce Flow |
pH: No | Pramary Produce pH |
Measurement Range: | |
onductivity: Feed Water: (0-2000) µSiem or (0-20000) µSiem; Primary Produce Water: (0-200 ) µSiem Secondary Produce Water: (0-20) µSiem pH: 0-14 | |
Acquire the Signal: | |
1.Raw Water Low Pressure; 2.Pramary boosterpump inlet Low-pressure; 3.Pramary booster pump outlet High-pressure; 4.Pramary produce tank high level; 5.Pramary produce tank low level; 6.Preprocessing Signal. | 1.Raw Water Low Pressure; 2.Pramary booster pump inlet Low-pressure; 3.Pramary booster pump outlet High-pressure; 4.Pramary produce tank high level; 5.Pramary produce tank low level; 6.Secondary Booster Pump Outlet High pressure; 7.Secondary Produce Tank Low Level; 8.Secondary Produce Tank High Level; 9.Preprocessing Signal |
Control Output: | |
1.Inlet Valve; 2.Primary Flush Valve; 3.Primary Drain Valve; 4.Antiscalant pump; 5.Feed Pump; 6.Pramary booster pump | 1.Inlet Valve; 2.Primary Flush Valve; 3.Primary Drain Valve; 4.Antiscalant pump; 5.Feed Pump; 6.Pramary booster pump 7. Secondary Booster Pump; 8.Secondary Flush Valve; 9. Secondary Drain Valve; 10.pH Acid-base adjustment pump |
Contro I Power: DC24V士4V | |
Dimensions: (203*145*55) mm | |
lnstallation Size: (192*138)mm Panel flushbonading mounting |